Measurement and metering transformer board, fully assembled module, with Metering cross, for the internal use, degree of protection IP2XC, applicable standards: EN 61439-1, EN 61439-2, EN 61439-3, Rated operational voltage 415V AC 50/60 Hz, rated current 220 A, Rated current of the assembly of switchgear and controlgear InA 200 A, in RAL 7035, dimensions in mm (H x W x D): 1350 x 500 x 160, Earthing system TN-S, 5-pole, Number of SG spaces 1, Number of transformer meter spaces 1, Pre-wired according requirements DSO, voltage path 3 low voltage path switches B10/25kA overvoltage path category 3, current transformer range CT mounting pad with CT rail 30 x 5 mm, parting point after the current transformer Switch 250 A / 3-pole and 2 fuse switch disconnectors NH00/160 A (M8), primary wiring Cu-Busbar 30 x 5 mm, Incomer and Outgoing connected to terminal screws, Connection N+PE (M8), Note: In case short circuit is > 25 kA, Backup protection required for voltage path circuit. Short circuit value to be obtained from DSO. Busbar terminals should be ordered seperately, Grid unit 9 GU, Overall height 5, panel width 2, Space units 216, covers out of Plastic, Quick sealable connection, RAL 7035