Measurement and metering transformer board for EEG, fully assembled module, with Metering cross, for the internal use, degree of protection IP2XC, applicable standards: EN 61439-1, EN 61439-2, Rated operational voltage 415V AC 50/60 Hz, rated current 115 A, Rated current of the assembly of switchgear and controlgear InA 115 A, in RAL 7035, dimensions in mm (H x W x D): 1350 x 500 x 160, Earthing system TN-S, 5-pole, Number of SG spaces 1, Number of transformer meter spaces 1, Pre-wired according requirements DSO, voltage path 3 low voltage path switches B10/25kA overvoltage path category 3, busbar system Cu busbars 12 x 5 mm 5-pole, parting point before the current transformer Fuse switch disconnector NH1/250A, primary wiring L1-L3 Cu-Busbar 30 x 5 und 25 x 5, PE+N Cu-Busbar 20 x 5 mm, Incomer grid connected to busbar Cu 12 x 5 mm, PV-connected to contactor, PE connected to terminal 50 qmm, complete with distribution and control wiring, Grid unit 9 GU, Overall height 5, panel width 2, Space units 216, covers out of Plastic, Quick sealable connection, RAL 7035