Measurement and metering transformer cabinet, series A, fully assembled cabinet, with Metering cross, Expansion option: Lateral, for the internal use, class of protection II (double insulated), degree of protection IP31, applicable standards: EN 61439-1, Rated operational voltage 415V AC 50/60 Hz, rated current 210 A, Rated current of the assembly of switchgear and controlgear InA 210 A, Powder-coated, in RAL 9016, enclosure out of Sheet steel / Plastic, single-leaf door, dimensions in mm (H x W x D): 1400 x 550 x 215, Earthing system TN-S, 5-pole, net side compartment, meter space: with busbar, Number of SG spaces 1, Number of transformer meter spaces 1, TAE terminal box 1, net side compartment, meter space: with busbar, Pre-wired according requirements DSO, voltage path Fuse base element D01/3-pole, busbar system Cu busbars 12 x 5 mm 5-pole, parting point before the current transformer Fuse switch disconnector NH1/250A, parting point after the current transformer 2 Fuse switch disconnector NH00/250 A (M10), primary wiring L1-L3 120 qmm, N+PE 120 qmm, Connection N+PE (M8), Grid unit 9 GU, Overall height 5, panel width 2, Space units 216, covers out of Plastic, Quick sealable connection, RAL 7035