Technical Information
Preces stāvoklis |
Jauns |
Ražotāja nosaukums |
KA4224Z Measurement and metering transformer board, Field width: 2, Rows: 0, 1350 mm x 500 mm x 160 mm, IP2XC |
Zīmols |
ABB
|
Kategorijas |
Sadales paneļi
|
Harmonizētās sistēmas kods |
8537 1098 00
|
Krāsa |
Pelēks |
Platums |
500 mm |
Modelis |
2-stāvu |
Augstums |
1350 mm |
RAL numurs |
7035 |
Ar montāžas plāksni |
No |
Savienojuma telpa |
300 mm |
Ar elektroinstalāciju |
Yes |
Platums moduļu atstarpju skaitā |
24 |
TSG paneļu skaits |
1 |
Izplatītāja rindu skaits |
0 |
Skaitītāju skapju skaits |
1 |
Apakšējā savienojuma vieta |
Ar kopņu joslu 5-polu |
Aizsardzības pakāpe (IP) |
IP2XC |
Galvenā slēdža nominālā strāva |
160 A |
Vāka modelis |
Slēgts ar iepriekšēju nostiprināšanu |
Iepakojuma informācija
Iepakojuma līmenis 1 |
4011617338758 |
Lejupielādes
Apraksts
Measurement and metering transformer board, fully assembled module, with Metering cross, for the internal use, degree of protection IP2XC, applicable standards: EN 61439-1, EN 61439-2, Rated operational voltage 415V AC 50/60 Hz, rated current 128 A, Rated current of the assembly of switchgear and controlgear InA 160 A, in RAL 7035, dimensions in mm (H x W x D): 1350 x 500 x 160, Earthing system TN-S, 5-pole, Number of SG spaces 1, Number of transformer meter spaces 1, Pre-wired according requirements DSO, voltage path Fuse base element D01/3-pole sealable, busbar system Cu busbars 12 x 5 mm 5-pole, parting point before the current transformer Fuse switch disconnector NH00/160A, current transformer range CT mounting pad with CT rail 170 x 30 x 5 mm, parting point after the current transformer Switch 160 A / 3-pole (10-70qmm), primary wiring 70 qmm, N+PE Connection N+PE 95qmm, Note: metering transformer sets to be installed in seperate housing. For DSO Cottbus cabinets have to be IP54. Incomer housing could be e.g. EK221, Grid unit 9 GU, Overall height 5, panel width 2, Space units 216, covers out of Plastic, Quick sealable connection, RAL 7035