Measurement and metering transformer board, fully assembled module, with Metering cross, for the internal use, degree of protection IP2XC, applicable standards: EN 61439-1, EN 61439-2, Rated operational voltage 415V AC 50/60 Hz, rated current 210 A, Rated current of the assembly of switchgear and controlgear InA 210 A, in RAL 7035, dimensions in mm (H x W x D): 1350 x 500 x 160, Metering module pre-wired, Earthing system TN-S, 5-pole, net side compartment, meter space: with busbar, Number of SG spaces 1, Number of transformer meter spaces 1, net side compartment, meter space: with busbar, Pre-wired according requirements DSO, voltage path Miniature circuit breaker B16/25 kA 3-pole overvoltage path catagory 3, busbar system Cu busbars 2 x 12 x 5 mm 5-pole, parting point before the current transformer Fuse base element NH2/400 A, current transformer range CT mounting pad out of support insulators with CT rail 160 x 30 x 10 mm, parting point after the current transformer Switch disconnector 250 A / 4-pole, primary wiring L1-L3, N 120 qmm, PE 95 qmm, Connection N+PE (M12), Grid unit 9 GU, Overall height 5, panel width 2, Space units 216, covers out of Plastic, Quick sealable connection, RAL 7035