Technical Information
Toote seisukord |
Uus |
Tootja nimi |
Low-Voltage Fan Coil Room Controller: BACnet MS/TP, Analog 0-10 Vdc, Commercial/Override |
Bränd |
Schneider Electric
|
Kategooriad |
Andurid
|
Paigaldusviis |
Pinnapealne |
Kooste ehitus |
Juhtelement |
Värvus |
Valge |
Pinnatöötlus |
Töötlemata |
Kuvariga |
Yes |
Materjal |
Termoplastist |
Siinisüsteem KNX |
No |
Raadiosageduslik siinisüsteem |
No |
Siinisüsteem Powernet |
No |
Siiniühendusega |
Yes |
Materjal |
Plast |
Muud siinisüsteemid |
Muul viisil |
Siinisüsteem LON |
No |
Vargusevastane/lahtimonteerimiskaitse |
Yes |
Käsisäte |
Yes |
Võimalik on paralleelne hooldus |
Yes |
Kohalolunupp |
Yes |
RAL-number (akin) |
9010 |
Kaitseaste (IP) |
IP20 |
LED näidikuga |
Yes |
Läbipaistev |
No |
Pinna liik |
Matt |
Lokaaljuhtimisega |
Yes |
Siinisüsteem KNX radio |
No |
Raadiosageduslik, kahesuunaline |
No |
Temperatuurijuhtimise klass |
VI |
Ooteoleku võimsustarve (solstandby) |
0 W |
Sisseehitatud paigalduskarbi vähim sügavus |
0 mm |
Pakendamise üksikasjad
Pakkimistase 1 |
0711426066951 |
Allalaadimised
Kirjeldus
SE7300 Series room controllers are used for Low Voltage Fan Coil Unit control. The room controllers rated supply voltage range is 10V to 30V AC at 50 or 60Hz. The rated operational power is 2VA. The Electrical insulation class is Class II. The room controller is equiped with a communication port that uses BACnet MS/TP protocol. Its Room and Outdoor Air Temperature Display Range is between -40 and 122 oF. The measurement accuracy is +/- 0.9 oF at 70oF typical calibration. The temperature setting range is 40…90oF for heating and 54 to 100 oF for cooling. The room controller is equiped with 1 dry contact input, 2 universal analog outputs, with 0 to 10V DC at 5mA into 2 kOhm resistance. The product follows the following standards: ICES-003, UL 873, FCC part 15 subpart B, CSA C22.2 No 24 It is certified for C-Tick : AS/NZS CISPR 22, FCC : CFR 47 part 15 class A, UL listed file E27734 CCN XPAX, UL listed file E27734 CCN XPAX7, CE. The humidity setting range is 10 to 90% for humidification, and 15 to 95% for dehumidification. The ambient air temperature for operation is between 32 and 122 oF. The relative humidity for operating or storage is between 0 and 95% non condensing.