Technical Information
Item condition |
New |
Manufacture name |
INT63 BEV.RE.3P 28-40/240-480A |
Brand |
Schneider Electric
|
Categories |
Accessories (Automatics & control)
|
Country of origin |
FR |
Harmonized System Code |
8538 9099 00
|
Rated permanent current Iu |
40 A |
Number of poles |
3 |
Short-circuit release function |
Undelayed |
Overload release current setting |
28-40 A |
With ground fault protection function |
No |
Initial value of the undelayed short-circuit release - setting range |
240 A |
End value adjustment range undelayed short-circuit release |
480 A |
Type of motor protection |
Thermal/magnetic release |
Voltage type for actuating |
Self powered |
Packing details
Packing level 1 |
3389110180688 |
Description
TeSys Integral thermal magnetic protection module, for mounting on contactor breakers LD1LD, LD4LD, LD5LD. With an adjustable thermal setting range Irth 28-40A, a tripping class 20, and a magnetic protection range 240-480A (6 to 12 Irth max), it protects motors 15 to 22kW@400V AC-43 for normal starting applications. It ensures phase imbalance protection and compensation of the thermal protection from -20 to 60°C. Manual reset is done by the control knob of the contactor breaker, remote reset requires an additional reset module mounted on the contactor breaker (to be ordered separately). Multi standards certified (IEC, UL, CSA, Marine), Green Premium compliant (RoHS/REACh).