Register to unlock your exclusive B2B prices and start shopping. Sign up now!
ÖLFLEX CLASSIC 100 SY 2X4 image 1
ÖLFLEX CLASSIC 100 SY 2X4 image 2
ÖLFLEX CLASSIC 100 SY 2X4 image 3
ÖLFLEX CLASSIC 100 SY 2X4 thumbnail 1
ÖLFLEX CLASSIC 100 SY 2X4 thumbnail 2
ÖLFLEX CLASSIC 100 SY 2X4 thumbnail 3

ÖLFLEX CLASSIC 100 SY 2X4

In stock: No Vendor stock: No Minimal order quantity: 1
Price (excl. VAT):
4,31 €
This price is valid until 24.12.24
EAN: 4044773028904
MPN: 0016101
Package: 1

Technical Information

Item condition New
Manufacture name ÖLFLEX CLASSIC 100 SY 2X4
Brand LAPP
Categories Cables and wires
Country of origin DE
Harmonized System Code 8544 4995 00
Nominal cross section conductor 4 mm²
Material core insulation Polyvinyl chloride (PVC)
Core identification Colour
Nominal voltage U 750 V
Colour outer sheath Colourless
Material outer sheath Polyvinyl chloride (PVC)
Conductor category Class 5 = flexible
Permitted cable outer temperature during assembling/handling -5-70 °C
Permitted cable outer temperature after assembling without vibration -40-80 °C
Number of cores 2
Halogen free according to IEC 60754-2 No
Low smoke according to IEC 61034-2 No
Outer diameter approx. 13.6 mm
Reaction-to-fire according to EN 13501-6: Class Eca
Reaction-to-fire according to EN 13501-6: Smoke production None
Reaction-to-fire according to EN 13501-6: Flaming droplets/particles None
Reaction-to-fire according to EN 13501-6: Acidity None
Min. permitted bending radius, stationary application/permanent installation 81.6 mm
Flame retardant according to IEC 60332-1-2 Yes
Flame retardant according to IEC 60332-3-21 (Cat A F/R) No
Flame retardant according to IEC 60332-3-22 (Cat A) No
Flame retardant according to IEC 60332-3-23 (Cat B) No
Flame retardant according to IEC 60332-3-24 (Cat C) No
Flame retardant according to IEC 60332-3-25 (Cat D) No
Halogen free according to IEC 60754-1 No
Halogen free according to IEC 60754-3 No

Packing details

Packing level 1 4044773028904, 4044774545721, 4044774545707

Downloads

Description

Voordelen; Extra mechanische bescherming door staaldraadomvlechting Toepassing; InstallatietechniekIndustriële machinesHVAC Gebieden met een hoge mechanische belasting