Technical Information
Item condition |
New |
Manufacture name |
TeSys Deca contactor - 3P(3 NO) - AC-3/AC-3e - = 440 V 32 A - 12 V DC coil |
Brand |
Schneider Electric
|
Categories |
Modular switches
|
Country of origin |
FR |
Harmonized System Code |
8536 4190 89
|
Modular version |
No |
Rated operation power at AC-3, 400 V |
15 kW |
Number of normally open contacts as main contact |
3 |
Number of normally closed contacts as main contact |
0 |
Number of auxiliary contacts as normally open contact |
1 |
Number of auxiliary contacts as normally closed contact |
1 |
Rated operation current Ie at AC-3, 400 V |
32 A |
Rated operation current Ie at AC-1, 400 V |
50 A |
Rated control supply voltage at DC |
12 V |
Type of electrical connection of main circuit |
Screw connection |
Voltage type for actuating |
DC |
Rated operation current Ie at AC-4, 400 V |
18 A |
Rated operation power at AC-4, 400 V |
7.5 kW |
Rated operation power NEMA |
0 kW |
Packing details
Packing level 1 |
3389110357677 |
Packing level 2 |
3389110357675 |
Downloads
Description
TeSys D contactor, 3 poles (3NO), for motor control applications up to 32A/690V AC-3/3e (15kW@400V). They can be used to create motor starters for almost any type of application. It provides a 12V DC coil with transient suppressor module, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh). When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.18 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.