Item condition |
New |
Manufacture name |
Type1+2+3 combined arrester DEHNshield ZP 2 SG for TN-S systems |
Brand |
Dehn
|
Categories |
Lighting protection
|
Country of origin |
DE |
Harmonized System Code |
8536 3090 00
|
Mounting method |
Busbar |
Lightning impulse current (10/350 µs) |
50 kA |
Number of poles |
4 |
Follow current extinguishing capability |
25 kA |
Max. continuous voltage AC |
255 V |
Nominal voltage AC |
230 V |
Test class |
Type 1 and 2 and 3 |
Signalling at the device |
Optic |
Degree of protection (IP) |
IP30 |
Voltage protection level N-PE |
1.5 kV |
Max. conductor cross section solid (solid, stranded) |
25 mm² |
Specific energy (W/R) |
39.06 kJ/Ohm |
Energy-coordinated protection effect with regard to the terminal equipment |
Yes |
System configuration TN-S |
Yes |
System configuration TT |
No |
Voltage protection level L-PE |
1.5 kV |
Max. overcurrent protection device, parallel connection (fuse) |
160 A |
Max. overcurrent protection device, series connection (fuse) |
160 A |
Voltage switching spark gap technology |
Yes |
Overcurrent protected voltage tapping |
Yes |