Register to unlock your exclusive B2B prices and start shopping. Sign up now!
MD01 image 1

VIGILOHM 12 CHANNEL FAULT LOCATOR - 100-440VAC/DC

In stock: No Vendor stock: No Minimal order quantity: 1
Price (excl. VAT):
585,83 €
This price is valid until 24.12.24
EAN: 3606489504830
MPN: IMDIFL12
Package: 1
Box: 8
Pallet: 64

Technical Information

Item condition New
Manufacture name VIGILOHM 12 CHANNEL FAULT LOCATOR - 100-440VAC/DC
Brand Schneider Electric
Categories Relays
Width 108 mm
Function For mixed system
Height 110 mm
Depth 59 mm
Rated frequency 45-65 Hz
With detachable clamps Yes
Line capacity 150 µF
Indication of insulation value No
Error registration possible No
Type of electric connection Screw connection
Rated voltage 0-1000 V
Rated control supply voltage at AC 50 Hz 100-440 V
Rated control supply voltage at AC 60 Hz 100-440 V
Rated control supply voltage at DC 100-440 V
Voltage type for actuating AC
Number of contacts as normally closed contact 0
Number of contacts as normally open contact 0
Number of contacts as change-over contact 1

Packing details

Packing level 1 3606489504830
Packing level 2 3606489504834
Packing level 3 3606489504830

Downloads

Description

This device belongs to the Vigilohm range designed to monitor ungrounded/IT electrical networks at feeder level, in accordance to installation and products standards This insulation fault location is only possible when it is associated to IM400 series, XM300 or XM200. This device is dedicated to monitoring 12 feeders, AC, DC and ACDC, up to the toroid limit, 1000V. Configuration is set from the front of the device, through the HMI screen. Settings are related to alarm thresholds. It displays which feeder has an insulation fault. Auto-test starts automatically every 5 hours, and on demand. In case the insulation resistance drops below the set threshold, an alarm is triggered thru the IFL output relay and HMI. Once no fault is monitored, the alarm is cleared, the alarm relay is back to normal. The device can be supplied by a 110VAC to 440VAC source or a 110VDC to 440VDC, all with a tolérence of plus or minus 15%.