EAN: 4013364275331
MPN: 941405
Package: 1

Technical Information

Item condition New
Manufacture name Appl.-opt. combined arrester DEHNshield type 1+2 for three-phase TN-S
Brand Dehn
Categories Lighting protection
Country of origin DE
Harmonized System Code 8536 3090 00
Mounting method DIN rail (top hat rail) 35 mm
Lightning impulse current (10/350 µs) 50 kA
Number of poles 4
Construction size 4 modular spacing
Remote signalling Yes
Follow current extinguishing capability 25 kA
Max. continuous voltage AC 255 V
Nominal voltage AC 230 V
Test class Type 1 + 2
Signalling at the device Optic
Degree of protection (IP) IP20
Voltage protection level N-PE 1.5 kV
Max. conductor cross section solid (solid, stranded) 35 mm²
Max. conductor cross section flexible (fine-strand) 25 mm²
Specific energy (W/R) 625 kJ/Ohm
Energy-coordinated protection effect with regard to the terminal equipment Yes
System configuration TN-S Yes
Voltage protection level L-PE 1.5 kV
Max. overcurrent protection device, parallel connection (fuse) 160 A
Max. overcurrent protection device, series connection (fuse) 100 A
Voltage switching spark gap technology Yes

Packing details

Packing level 1 4013364275331, 4013364275331

Downloads

Description

Application-optimised multipole type 1 and type 2 DEHNshield spark-gap-based combined lightning current and surge arrester (according to EN 61643-11). Compact design due to space-saving spark gap technology with a width of only 1 module / pole. For use in residential buildings and special applications. Capable of protecting terminal equipment. For protecting low-voltage consumer installations against surges, even in case of direct lightning strikes. For installation in conformity with the lightning protection zone concept at the boundaries from 0A – 2.