Technical Information
Item condition |
New |
Manufacture name |
Residual current circuit breaker (RCCB), 40A, 2 p, 30mA, type G/A |
Brand |
EATON
|
Categories |
Leakage protection
|
Country of origin |
RS |
Harmonized System Code |
8536 2010 00
|
Mounting method |
DIN rail |
Voltage type |
AC |
Built-in depth |
69.5 mm |
Rated current |
40 A |
Rated voltage |
230 V |
Rated insulation voltage Ui |
440 V |
Number of poles |
2 |
Rated fault current |
0.03 A |
Leakage current type |
A |
Selective protection |
No |
Short-circuit breaking capacity (Icw) |
10 kA |
Surge current capacity |
0.25 kA |
Pollution degree |
2 |
Width in number of modular spacings |
2 |
Short-time delayed tripping |
Yes |
Explosion-proof |
No |
Frequency |
50 Hz |
Degree of protection (IP) |
IP20 |
Connectable conductor cross section solid-core |
1.5-35 mm² |
Connectable conductor cross section multi-wired |
1.5-16 mm² |
With interlocking device |
Yes |
Ambient temperature during operating |
-25-40 °C |
Additional equipment possible |
Yes |
Rated impulse withstand voltage Uimp |
4 kV |
Packing details
Packing level 1 |
4015081633128 |
Packing level 2 |
9008790458354, 9008790458354 |
Description
Residual current circuit-breaker PF7, 2 pole, Rated current In: 40 A, Rated short-circuit strength Icn: 10 kA, Rated fault current IΔN: 0.03 A, Type G/A (ÖVE E 8601), Pulse-current sensitive, Surge-proof, 3 kA, Switchgear for residential and commercial applications