Register to unlock your exclusive B2B prices and start shopping. Sign up now!
Coordin. lightning current arr. Type 1 DEHNbloc M w. high follow curre image 1
Coordin. lightning current arr. Type 1 DEHNbloc M w. high follow curre image 2
Coordin. lightning current arr. Type 1 DEHNbloc M w. high follow curre image 3
Coordin. lightning current arr. Type 1 DEHNbloc M w. high follow curre thumbnail 1
Coordin. lightning current arr. Type 1 DEHNbloc M w. high follow curre thumbnail 2
Coordin. lightning current arr. Type 1 DEHNbloc M w. high follow curre thumbnail 3

Coordin. lightning current arr. Type 1 DEHNbloc M w. high follow curre

In stock: No Vendor stock: No Minimal order quantity: 1 Not Available
Estimate delivery time at our warehouse (approx.): By request

Technical Information

Item condition New
Manufacture name Coordin. lightning current arr. Type 1 DEHNbloc M w. high follow curre
Brand Dehn
Country of origin DE
Harmonized System Code 8536 3090 00
Mounting method DIN rail (top hat rail) 35 mm
Lightning impulse current (10/350 µs) 25 kA
With remote signalling contact Yes
Number of conductors (without earthing) 1
Construction size 2 modular spacing
Voltage protection level 2.5 kV
Follow current extinguishing capability 50 kA
Max. continuous voltage AC 320 V
Nominal voltage AC 277 V
Category type 1 Yes
Signalling at the device Optic
Degree of protection (IP) IP20
Max. conductor cross section solid (solid, stranded) 50 mm²
Max. conductor cross section flexible (fine-strand) 35 mm²
Specific energy (W/R) 156.25 kJ/Ohm
System configuration TN Yes
System configuration TN-C Yes
System configuration TN-S Yes
System configuration TT Yes
System configuration TN-C-S Yes

Packing details

Packing level 1 4013364118645, 4013364118645

Downloads

Description

Single-pole DEHNbloc modular and coordinated spark-gap-based lightning current arrester ( type 1 according to EN 61643-11) consisting of a base part and plug-in protection module. Maximum system availability due to RADAX Flow follow current limitation. For protecting low-voltage consumer´s installations against surges and even direct lightning strikes. For installation in conformity with the lightning protection zone concept at the boundaries from 0A – 1.