Technical Information
Item condition |
New |
Manufacture name |
current transformer tropicalised DIN mount 400 5 cables d. 27 - bars 10x32 15x25 |
Brand |
Schneider Electric
|
Categories |
Indicators network parameters values
|
Country of origin |
TN |
Harmonized System Code |
8504 3180 90
|
Model |
Through-feed current converter |
Opening diameter |
27 mm |
Number of primary inputs |
1 |
With copper rail |
No |
Primary rated current |
400 A |
Snap mounting |
No |
Secondary rated apparent power |
12 VA |
Secondary rated current |
5 A |
Overcurrent limiting factor |
FS 5 |
With shock protection |
No |
Calibrated |
No |
Accuracy class |
1 |
Height opening |
15 mm |
Width opening |
25 mm |
Secondary connection |
Screw connection |
Packing details
Packing level 1 |
3606480618819 |
Packing level 2 |
3606480618814 |
Downloads
Description
This current transformer, tropicalised for busbar and cable, has a line rated current of 400 A and a secondary current rating of 5 A. This current transformer allow a maximum cable outer diameter of 27 mm. Compatible with a double output for bar: 32.5 mm x 10.5 mm or 25.5 mm x 15.5 mm. Burden and accuracy class as follows: class 0.5 maximum power: 10 VA, class 1 maximum power: 12 VA.