Technical Information
Item condition |
New |
Manufacture name |
Electronic RCD/MCB combination, 6 A, 30 mA, MCB trip characteristic: C, 1p, RCD trip characteristic: A |
Brand |
EATON
|
Categories |
Leakage protection
|
Country of origin |
CZ |
Harmonized System Code |
8536 2010 00
|
Voltage type |
AC |
Built-in depth |
69.5 mm |
Rated current |
6 A |
Rated voltage |
240 V |
Release characteristic |
C |
Rated insulation voltage Ui |
500 V |
Rated fault current |
0.03 A |
Leakage current type |
A |
Surge current capacity |
0.25 kA |
Current limiting class |
3 |
Over voltage category |
3 |
Pollution degree |
2 |
Width in number of modular spacings |
1 |
Frequency |
50/60 Hz |
Degree of protection (IP) |
IP20 |
Number of protected poles |
1 |
Concurrently switching neutral conductor |
No |
Rated short-circuit breaking capacity according to IEC 60947-2 |
0 kA |
Connectable conductor cross section solid-core |
1-25 mm² |
Connectable conductor cross section multi-wired |
1-25 mm² |
With interlocking device |
No |
Ambient temperature during operating |
-25-40 °C |
Flush-mounted installation |
No |
Number of poles (total) |
1 |
Anti-nuisance tripping version |
No |
Rated impulse withstand voltage Uimp |
4 kV |
Rated short-circuit breaking capacity Icn according to EN 61009-1 |
10 kA |
Disconnection characteristic |
Undelayed |
Rated short-circuit breaking capacity according to EN 61009 |
10 kA |
Packing details
Packing level 1 |
4015081489329 |
Packing level 2 |
9008790343339 |
Description
High-quality residual current device/miniature circuit breaker combination, line voltage-dependent, design width of one module unit only, specific for applications in the BS-distribution systems, permanently connected neutral conductors, contact position indicator red - green, comprehensive range of accessories suitable for subsequent installation, guide for secure terminal connection, wide range of rated fault currents, rated operational currents up to 45 A, tripping characteristics B, C, D, rated breaking capacity 10 kA