Technical Information
Item condition |
New |
Manufacture name |
FRCMM-40/2/03-S/A-RT Eaton Moeller series xEffect - FRCmM-NA RCCB |
Brand |
EATON
|
Categories |
Leakage protection
|
Country of origin |
RS |
Harmonized System Code |
8536 2010 00
|
Mounting method |
DIN rail |
Voltage type |
AC |
Built-in depth |
70.5 mm |
Rated current |
40 A |
Rated voltage |
240 V |
Rated insulation voltage Ui |
440 V |
Number of poles |
2 |
Rated fault current |
0.3 A |
Leakage current type |
A |
Selective protection |
No |
Short-circuit breaking capacity (Icw) |
10 kA |
Surge current capacity |
5 kA |
Pollution degree |
2 |
Width in number of modular spacings |
2 |
Short-time delayed tripping |
No |
Explosion-proof |
No |
Frequency |
50/60 Hz |
Degree of protection (IP) |
IP20 |
Connectable conductor cross section solid-core |
1.5-35 mm² |
Connectable conductor cross section multi-wired |
1.5-16 mm² |
With interlocking device |
No |
Ambient temperature during operating |
-25-75 °C |
Additional equipment possible |
No |
Rated impulse withstand voltage Uimp |
4 kV |
Packing details
Packing level 1 |
9010238213708 |
Packing level 2 |
9010238213951, 9010238213951 |
Description
Residual current circuit-breaker FRCmM, 2 pole, Rated current In: 40 A, Rated short-circuit strength Icn: 10 with back-up fuse kA, Rated fault current IΔN: 0.3 A, Switchgear for industrial and advanced commercial applications