Register to unlock your exclusive B2B prices and start shopping. Sign up now!
iPRD40r modular surge arrester - 4P - 350V - with remote transfert image 1
MD01 image 2
iPRD40r modular surge arrester - 4P - 350V - with remote transfert image 3
iPRD40r modular surge arrester - 4P - 350V - with remote transfert image 4
iPRD40r modular surge arrester - 4P - 350V - with remote transfert image 5
iPRD40r modular surge arrester - 4P - 350V - with remote transfert thumbnail 1
MD01 thumbnail 2
iPRD40r modular surge arrester - 4P - 350V - with remote transfert thumbnail 3
iPRD40r modular surge arrester - 4P - 350V - with remote transfert thumbnail 4
iPRD40r modular surge arrester - 4P - 350V - with remote transfert thumbnail 5

iPRD40r modular surge arrester - 4P - 350V - with remote transfert

In stock: No Vendor stock: No Minimal order quantity: 1
Price (excl. VAT):
79,11 €
This price is valid until 31.12.24
EAN: 3606480506338
MPN: A9L40401
Package: 1
Box: 3

Technical Information

Item condition New
Manufacture name iPRD40r modular surge arrester - 4P - 350V - with remote transfert
Brand Schneider Electric
Categories Lighting protection
Country of origin CN
Harmonized System Code 8536 3030 99
Mounting method DIN rail (top hat rail) 35 mm
With remote signalling contact Yes
Number of conductors (without earthing) 4
Construction size 4 modular spacing
Voltage protection level 1.6 kV
Max. continuous voltage AC 350 V
Nominal discharge surge current (8/20) 15 kA
Nominal voltage AC 350 V
Nominal voltage DC 0 V
Category type 2 Yes
Voltage protection level L-N 0 kV
Signalling at the device Optic
Max. continuous voltage DC 0 V
Degree of protection (IP) IP20
Max. PV-voltage 0 V
Voltage protection level N-PE 1.6 kV
Integrated backup fuse No
Max. conductor cross section solid (solid, stranded) 25 mm²
Max. conductor cross section flexible (fine-strand) 16 mm²
System configuration DC No
System configuration IT No
System configuration TN No
System configuration TN-C Yes
System configuration TN-S No
System configuration TT No
System configuration other No
System configuration TN-C-S No
Max. discharge surge current (8/20) 40 kA
Short-circuit breaking capacity (Isccr) 50 kA
Max. overcurrent protection device, parallel connection (fuse) 0 A
Max. overcurrent protection device, series connection (fuse) 0 A
Integrated short-circuit protection No
Integrated short-circuit protection selective to fuse gG 0 A
Leakage-current free No

Packing details

Packing level 1 3606480506338
Packing level 2 3606480506335
Packing level 3 3606480506336

Downloads

Description

This Acti9 iPRD40r surge arrester protects 4P installations. It allows quick replacement of damaged cartridges. This Type 2 device is recommended for high risk level in incoming panel board. It offers remote reporting of the "cartridge must be changed" message. It can be turned over to allow the phase/neutral/earth cables to enter through either the top or the bottom. The associated circuit breaker Isc breaking capacity can go up to 50kA. It is compatible with TT and TN-S earthing system. The Uc maximum continuous operating voltage in common mode (L/PE or N/PE) is 350VAC. The Up maximum voltage protection level in common mode (L/PE or N/PE) is 1.4kV. The Ue rated operational voltage is 230VAC +/- 10%. The product colour is white (RAL9003).The dimensions are (W) 72mm x (H) 85mm x (D) 69mm. The weight is 422g. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 85°C. This product is compliant with EN 61643-11 and IEC 61643-11 standards.