Initial value of the undelayed short-circuit release - setting range
135 A
End value adjustment range undelayed short-circuit release
540 A
Type of motor protection
Other
Voltage type for actuating
AC/DC
Packing details
Packing level 1
3606481493774
Description
TeSys U magnetic control unit to be inserted in power bases LUB38 to form a TeSys U starter controller, for 3-phase motor applications up to 18.5kW@400V. It provides short circuit protection to motors with a rated current In 9.5-38A (In adjustable by dial), overcurrent protection level at 14.2 x In. To be used when a power base is connected to a motor drive or a soft starter providing overload protection. To be used with a 110-240V AC / 110-220V DC voltage for the control of the starter (through the control terminals A1/A2 located in the power base). Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).