Technical Information
Item condition |
New |
Manufacture name |
Motor circuit breaker, TeSys Deca, 3P, 37-50 A, thermal magnetic, EverLink terminals |
Brand |
Schneider Electric
|
Categories |
Motor protection circuit-breakers
|
Country of origin |
FR |
Harmonized System Code |
8536 2010 90
|
Width |
55 mm |
Height |
132 mm |
Depth |
136 mm |
Rated operation power at AC-3, 400 V |
22 kW |
With integrated auxiliary switch |
No |
Rated permanent current Iu |
50 A |
With integrated under voltage release |
No |
Number of poles |
3 |
Rated operating voltage |
690 V |
Overload release current setting |
37-50 A |
Degree of protection (IP) |
IP20 |
With thermal protection |
Yes |
Type of electrical connection of main circuit |
Screw connection |
Type of control element |
Turn button |
Switch off technique |
Thermomagnetic |
Rated operation power at AC-3, 230 V |
15 kW |
Rated short-circuit breaking capacity lcu at 400 V, AC |
50 kA |
Adjustment range undelayed short-circuit release |
700 A |
Phase failure sensitive |
Yes |
Device construction |
Complete device in housing |
Packing details
Packing level 1 |
3389119405409 |
Packing level 2 |
3389119405409 |
Downloads
Description
TeSys GV motor circuit breaker, 3 poles (3P), 50A/690V, for 3-phase motor applications 22kW@400V. It provides a thermal-magnetic protection with a thermal setting range 37-50A, magnetic tripping at 14xIn, high breaking capacity Icu 50kA@400V. Connection by Everlink BTR screw terminals. Start-stop control by rotary knob guaranteed for 50 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).