Register to unlock your exclusive B2B prices and start shopping. Sign up now!
Motor circuit breaker, TeSys Deca, 3P, 37-50 A, thermal magnetic, upstream EverLink terminals image 1
MD01 image 2
MD01 image 3
Motor circuit breaker, TeSys Deca, 3P, 37-50 A, thermal magnetic, upstream EverLink terminals image 4
Motor circuit breaker, TeSys Deca, 3P, 37-50 A, thermal magnetic, upstream EverLink terminals image 5
Motor circuit breaker, TeSys Deca, 3P, 37-50 A, thermal magnetic, upstream EverLink terminals image 6
Motor circuit breaker, TeSys Deca, 3P, 37-50 A, thermal magnetic, upstream EverLink terminals thumbnail 1
MD01 thumbnail 2
MD01 thumbnail 3
Motor circuit breaker, TeSys Deca, 3P, 37-50 A, thermal magnetic, upstream EverLink terminals thumbnail 4
Motor circuit breaker, TeSys Deca, 3P, 37-50 A, thermal magnetic, upstream EverLink terminals thumbnail 5
Motor circuit breaker, TeSys Deca, 3P, 37-50 A, thermal magnetic, upstream EverLink terminals thumbnail 6

Motor circuit breaker, TeSys Deca, 3P, 37-50 A, thermal magnetic, upstream EverLink terminals

In stock: No Vendor stock: No Minimal order quantity: 1
Price (excl. VAT):
95,57 €
This price is valid until 24.12.24
EAN: 3389119412261
MPN: GV3P501
Package: 1
Pallet: 60

Technical Information

Item condition New
Manufacture name Motor circuit breaker, TeSys Deca, 3P, 37-50 A, thermal magnetic, upstream EverLink terminals
Brand Schneider Electric
Categories Motor protection circuit-breakers
Country of origin FR
Harmonized System Code 8536 2090 90
Width 55 mm
Height 111 mm
Depth 136 mm
Rated operation power at AC-3, 400 V 22 kW
With integrated auxiliary switch No
Rated permanent current Iu 50 A
With integrated under voltage release No
Number of poles 3
Rated operating voltage 0-690 V
Overload release current setting 37-50 A
Degree of protection (IP) IP20
With thermal protection Yes
Type of electrical connection of main circuit Screw connection
Type of control element Turn button
Switch off technique Thermomagnetic
Rated operation power at AC-3, 230 V 15 kW
Rated short-circuit breaking capacity lcu at 400 V, AC 50 kA
Adjustment range undelayed short-circuit release 700 A
Phase failure sensitive Yes
Device construction Complete device in housing

Packing details

Packing level 1 3389119412261
Packing level 2 3389119412261

Downloads

Description

TeSys GV motor circuit breaker, 3 poles (3P), 50A/690V, for 3-phase motor applications 22kW@400V. It provides a thermal-magnetic protection with a thermal setting range 37-50A, magnetic tripping at 14xIn, high breaking capacity Icu 50kA@400V. Upstream connection by Everlink BTR screw terminals, without downstream power terminal block for a direct assembly with a LC1D40A to D80A contactor. Start-stop control by rotary knob guaranteed for 50 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).