Technical Information
Item condition |
New |
Manufacture name |
Motor circuit breaker, TeSys GV4, 3P, 25A, Icu 25kA, thermal magnetic multifunction, lugs terminals |
Brand |
Schneider Electric
|
Categories |
Motor protection circuit-breakers
|
Country of origin |
PL |
Harmonized System Code |
8536 2010 90
|
Width |
81 mm |
Height |
155 mm |
Depth |
116 mm |
Rated operation power at AC-3, 400 V |
11 kW |
With integrated auxiliary switch |
No |
Rated permanent current Iu |
25 A |
With integrated under voltage release |
No |
Number of poles |
3 |
Rated operating voltage |
0-690 V |
Overload release current setting |
10-25 A |
Degree of protection (IP) |
IP40 |
With thermal protection |
Yes |
Type of electrical connection of main circuit |
Screw connection |
Type of control element |
Rocker lever |
Switch off technique |
Electronic |
Rated operation power at AC-3, 230 V |
5.5 kW |
Rated short-circuit breaking capacity lcu at 400 V, AC |
25 kA |
Adjustment range undelayed short-circuit release |
425 A |
Phase failure sensitive |
Yes |
Device construction |
Complete device in housing |
Packing details
Packing level 1 |
3606481310750 |
Packing level 2 |
3606481310758 |
Packing level 3 |
3606481310750 |
Downloads
Description
TeSys GV motor circuit breaker, 3 poles (3P), 25A/690V, for protection of 3-phase motors 5.5-11kW@400V. Multifunction circuit breaker, it provides thermal magnetic protection and advanced motor protection, breaking capacity Icu 25kA@400V, start-stop control by toggle, connection for bars or cables with lugs. Thermal protection adjustable by dials with a setting current Ir in range 10-25A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Advanced protections are adjustable with a smartphone using wireless NFC and include short time delay protection Isd with a setting range 5-13 Ir, phase unbalance and loss protection, ground fault protection, locked rotor (jam), long start. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). It can be equiped externally with 1 or 2 auxiliary SDx modules in order to have alarming and fault differentiation. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).