Technical Information
Item condition |
New |
Manufacture name |
OVR K10T1/PTC Surge Protective Device |
Brand |
ABB
|
Categories |
Lighting protection
|
Harmonized System Code |
8536 3010 00
|
Mounting method |
On basic element |
Connection 1 |
Other |
Frequency |
20 MHz |
Lightning impulse current (10/350 µs) |
1 kA |
With remote signalling contact |
No |
Limiting frequency |
20 MHz |
Explosion-tested version |
No |
Max. continuous voltage AC |
296 V |
Nominal discharge surge current (8/20) |
5 kA |
Nominal load current |
0.145 A |
Voltage protection level core/core |
395 V |
Voltage protection level core/earth |
395 V |
Signalling at the device |
None |
Voltage protection level core/signal ground |
395 V |
Voltage protection level signal ground/protective ground |
395 V |
Nominal voltage AC |
296 V |
Pro-active thermo-control |
No |
Signal disconnection |
- |
Packing details
Packing level 1 |
5415022372748 |
Downloads
Description
Kombinierte Überspannungs-Schutzeinrichtung für Daten-, Signal- und Telekommunkationstechnik, geprüft in den Kategorien D, C, B gemäß IEC/EN 61643 für blitzintensive Umgebungen, zur Verwendung an den Blitzschutzzonen LPZ 0 bis 3. Anschlusstechnik LSA-PLUS