Technical Information
Item condition |
New |
Manufacture name |
Phase monitoring relays, Multi-functional, 350 - 580 V AC, 50/60 Hz |
Brand |
EATON
|
Categories |
Relays
|
Country of origin |
DE |
Harmonized System Code |
8536 4900 00
|
Width |
45 mm |
Height |
85.6 mm |
Depth |
107 mm |
Voltage measuring range |
350-580 V |
With detachable clamps |
No |
Phase sequence monitoring |
Yes |
Phase failure detection |
Yes |
Function under voltage detection |
Yes |
Function over voltage detection |
Yes |
Phase imbalance monitoring |
Yes |
Type of electric connection |
Screw connection |
Rated control supply voltage at AC 50 Hz |
350-580 V |
Rated control supply voltage at AC 60 Hz |
350-580 V |
Rated control supply voltage at DC |
0 V |
Max. permitted delay-on energization time |
30 s |
Min. adjustable delay-on energization time |
0.1 s |
Max. permitted off-delay time |
30 s |
Min. adjustable off-delay time |
0.1 s |
Voltage type for actuating |
AC |
Number of contacts as normally closed contact |
0 |
Number of contacts as normally open contact |
0 |
Number of contacts as change-over contact |
2 |
Packing details
Packing level 1 |
4015081788019 |
Description
Phase monitoring relays, Product range: EMR Measuring and monitoring relays, Multi-functional, Power supply from the measuring circuit, On-delay/off-delay: none = 0 or adjustable between 0.1 - 30 s, Imbalance threshold values adjustable 2 - 25 % of mean value of phase voltages, Three-phase networks, Automatic phase sequence correction (can be disabled), Monitoring voltage per phase: UN= 350 - 580 V AC, 50/60 Hz V AC, Monitoring of: Phase sequence (can be deactivated), Phase failure, Overvoltage, Undervoltage, Imbalance, Phase sequence, Supply voltage: 350 - 580 V AC, 50/60 Hz, Mounting position: As required, Fixing: Snap fixing , top-hat rail IEC/EN 60715, Width: 45 mm, Standards: IEC, UL, CSA, CCC, GL