SPZT123-300/3+NPE-S Eaton Moeller series xPole - SPZT123 surge protection device image 1

SPZT123-300/3+NPE-S Eaton Moeller series xPole - SPZT123 surge protection device

In stock: No Vendor stock: No Minimal order quantity: 1
Price (excl. VAT):
479,64 €
This price is valid until 24.12.24
EAN: 9010653032755
MPN: EP-501043
Package: 1
Box: 24

Technical Information

Item condition New
Manufacture name SPZT123-300/3+NPE-S Eaton Moeller series xPole - SPZT123 surge protection device
Brand EATON
Categories Lighting protection
Country of origin SI
Harmonized System Code 8536 3090 00
Mounting method Busbar
Lightning impulse current (10/350 µs) 7.5 kA
Number of poles 4
Construction size 2 modular spacing
Voltage protection level 1.5 kV
Remote signalling No
Follow current extinguishing capability 0.1 kA
Max. continuous voltage AC 300 V
Nominal voltage AC 240 V
Test class Type 1 and 2 and 3
Voltage protection level L-N 1.5 kV
Signalling at the device Optic
Degree of protection (IP) IP20
Voltage protection level N-PE 1.5 kV
Integrated backup fuse No
Specific energy (W/R) 14 kJ/Ohm
Energy-coordinated protection effect with regard to the terminal equipment Yes
System configuration DC No
System configuration IT No
System configuration TN Yes
System configuration TN-C Yes
System configuration TN-S Yes
System configuration TT Yes
System configuration other No
System configuration TN-C-S Yes
Max. overcurrent protection device, parallel connection (fuse) 160 A
Max. overcurrent protection device, series connection (fuse) 160 A
Voltage switching spark gap technology Yes
Overcurrent protected voltage tapping Yes

Packing details

Packing level 1 9010653032755
Packing level 2 9010238227798

Description

For the protection of consumer systems in the mains connection compartment of the meter cabinet on a 40-mm bus bar, against transient overvoltages caused by direct and indirect lightning strikes, as well as switching operations. Meets all requirements for the installation of overvoltage protection according to DIN VDE 0100-534, test classes I, II, III according to IEC 61643-1, SPD type T1+2+3, conforms to IEC 61643-11: 2011, EN 61643-11: 2012+A11: 2018, lightning protection classes III and IV according to IEC 62305, leakage current-free, with integrated fuse for protecting the SmartMeterGateway and the APZ