Register to unlock your exclusive B2B prices. Register now
Contactor, 3 pole, 380 V 400 V 3 kW, 1 NC, 110 V DC, DC operation, Spr image 1
Contactor, 3 pole, 380 V 400 V 3 kW, 1 NC, 110 V DC, DC operation, Spr image 2
Contactor, 3 pole, 380 V 400 V 3 kW, 1 NC, 110 V DC, DC operation, Spr image 3
Contactor, 3 pole, 380 V 400 V 3 kW, 1 NC, 110 V DC, DC operation, Spr image 4
Contactor, 3 pole, 380 V 400 V 3 kW, 1 NC, 110 V DC, DC operation, Spr image 5

Contactor, 3 pole, 380 V 400 V 3 kW, 1 NC, 110 V DC, DC operation, Spr

In stock price (excl. VAT):
22,62 €
This price is valid until 2024-12-31
Price per m: 22,62 €
EAN: 4015082774394
MPN: 277439
Our warehouse: No Vendor stock: No
Per package: 1 Per box: N/A
Technical data
Item condition New
Manufacture name Contactor, 3 pole, 380 V 400 V 3 kW, 1 NC, 110 V DC, DC operation, Spr
Brand EATON
Categories Modular switches
Country of origin RO
Harmonized System Code 8536 4900 00
Modular version No
Rated operation power at AC-3, 400 V 3 kW
Number of normally open contacts as main contact 3
Number of normally closed contacts as main contact 0
Number of auxiliary contacts as normally open contact 0
Number of auxiliary contacts as normally closed contact 1
Rated operation current Ie at AC-3, 400 V 7 A
Rated operation current Ie at AC-1, 400 V 22 A
Rated control supply voltage at AC 50 Hz 0 V
Rated control supply voltage at AC 60 Hz 0 V
Rated control supply voltage at DC 110 V
Type of electrical connection of main circuit Spring clamp connection
Voltage type for actuating DC
Rated operation current Ie at AC-4, 400 V 5 A
Rated operation power at AC-4, 400 V 2.2 kW
Rated operation power NEMA 2.2 kW
Packing details
Packing level 1 4015082774394
Downloads
Description
Contactor, Application: Contactors for Motors, Contactors up to 170 A, 3 pole, Utilization category: AC-1: Non-inductive or slightly inductive loads, resistance furnaces, NAC-3: Normal AC induction motors: starting, switch off during running, AC-4: Normal AC induction motors: starting, plugging, reversing, inching, Connection technique: Spring-loaded terminals, Notes: Also suitable for motors with efficiency class IE3, Number of poles: 3 pole, Rated operational current AC-3 380 V 400 V: Ie= 7 A, Rated operational current AC-1 Conventional free air thermal current, 3 pole, 50 - 60 Hz Open at 40 °C: Ith =Ie= 22 A, enclosed: Ith= 18 A, Rated operational current AC-1 Conventional free air thermal current, 1 pole open: Ith= 50 A, enclosed: Ith= 45 A, Max. rating for three-phase motors, 50 - 60 Hz AC-3 220 V 230 V: P= 2.2 kW, 380 V 400 V: P= 3 kW, 660 V 690 V: P= 3.5 kW, Max. rating for three-phase motors, 50 - 60 Hz AC-4 220 V 230 V: P= 1 kW, 380 V 400 V: P= 2.2 kW, 660 V 690 V: P= 2.9 kW, Can be combined with auxiliary contact: DILA-XHIC(V).., Contacts N/C = Normally closed: 1 NC, Instructions: Contacts to EN 50 012., Auxiliary current, coil, and main current terminals with spring-cage connection technology., Integrated varistor suppressor circuit., with mirror contact., Voltage AC/DC: DC operation

Accessories

Suitable for

Accessories
4015082764289 4015082765279 4015082765330 4015082765347 4015082765323
Suitable for
4015082764265 4015082764258 4015082764210 4015082764272 4015082764289 4015082764296 4015082765279 4015082765330 4015082765347 4015082765323