Number of normally closed contacts as main contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Rated operation current Ie at AC-3, 400 V
40 A
Rated operation current Ie at AC-1, 400 V
63 A
Rated control supply voltage at AC 50 Hz
110 V
Rated control supply voltage at AC 60 Hz
120 V
Rated control supply voltage at DC
0 V
Type of electrical connection of main circuit
Screw connection
Voltage type for actuating
AC
Rated operation current Ie at AC-4, 400 V
25 A
Rated operation power at AC-4, 400 V
12 kW
Rated operation power NEMA
22 kW
Packing details
Packing level 1
4015081094165
Description
Contactor, Application: Contactors for 4 pole electric consumers, Contactors up to 200 A, 4 pole, Utilization category: AC-1: Non-inductive or slightly inductive loads, resistance furnaces, NAC-3: Normal AC induction motors: starting, switch off during running, Connection technique: Screw terminals, Number of poles: 4 pole, 380 V 400 V: Ie= 40 A, Conventional free air thermal current, 3 pole, 50 - 60 Hz Open at 40 °C: Ith =Ie= 63 A, enclosed: Ith= 50 A, Conventional free air thermal current, 1 pole open: Ith= 162 A, enclosed: Ith= 146 A, 220 V 230 V: P= 12.5 kW, 380 V 400 V: P= 18.5 kW, 660 V 690 V: P= 23 kW , Instructions: Contacts to EN 50 012., Voltage AC/DC: AC operation