Item condition | New |
Manufacture name | OVR T2 40-275s C QS Surge Protective Device |
Brand | ABB |
Categories |
Lighting protection |
Harmonized System Code | 8536 3090 00 |
Mounting method | DIN rail (top hat rail) 35 mm |
With remote signalling contact | Yes |
Number of conductors (without earthing) | 1 |
Construction size | 4 modular spacing |
Voltage protection level | 1.4 kV |
Max. continuous voltage AC | 275 V |
Nominal discharge surge current (8/20) | 20 kA |
Nominal voltage AC | 230 V |
Nominal voltage DC | 320 V |
Category type 2 | Yes |
Voltage protection level L-N | 1.4 kV |
Signalling at the device | Optic |
Max. continuous voltage DC | 355 V |
Degree of protection (IP) | IP20 |
Max. PV-voltage | 0 V |
Voltage protection level N-PE | 1.4 kV |
Integrated backup fuse | Yes |
Max. conductor cross section solid (solid, stranded) | 35 mm² |
Max. conductor cross section flexible (fine-strand) | 25 mm² |
System configuration DC | No |
System configuration IT | No |
System configuration TN | Yes |
System configuration TN-C | No |
System configuration TN-S | Yes |
System configuration TT | Yes |
System configuration other | No |
System configuration TN-C-S | Yes |
Max. discharge surge current (8/20) | 40 kA |
Short-circuit breaking capacity (Isccr) | 100 kA |
Max. overcurrent protection device, parallel connection (fuse) | 160 A |
Max. overcurrent protection device, series connection (fuse) | 160 A |
Integrated short-circuit protection | FALSE |
Leakage-current free | FALSE |
Packing level 1 | 3660308525352 |
Packing level 2 | 3660308525352 |