Register to unlock your exclusive B2B prices. Register now
Lightning current and surge arresters, 50kA, N-space unit image 1
Lightning current and surge arresters, 50kA, N-space unit image 2

Lightning current and surge arresters, 50kA, N-space unit

In stock price (excl. VAT):
195,03 €
This price is valid until 2024-12-31
Price per m: 195,03 €
EAN: 4015081787869
MPN: 184750
Our warehouse: No Vendor stock: No
Per package: 1 Per box: 30 Per pallet: N/A
Technical data
Item condition New
Manufacture name Lightning current and surge arresters, 50kA, N-space unit
Brand EATON
Categories Lighting protection
Country of origin RO
Harmonized System Code 8536 5080 00
Mounting method DIN rail (top hat rail) 35 mm
Lightning impulse current (10/350 µs) 12.5 kA
Number of poles 4
Construction size 4 modular spacing
Voltage protection level 1.5 kV
Remote signalling No
Follow current extinguishing capability 0 kA
Max. continuous voltage AC 260 V
Nominal voltage AC 240 V
Nominal voltage DC 0 V
Test class Type 1 + 2
Voltage protection level L-N 1.5 kV
Signalling at the device Optic
Max. continuous voltage DC 0 V
Degree of protection (IP) IP20
Max. PV-voltage 0 V
Voltage protection level N-PE 1.4 kV
Integrated backup fuse No
Max. conductor cross section solid (solid, stranded) 25 mm²
Max. conductor cross section flexible (fine-strand) 35 mm²
Voltage protection level (DC+ - DC-) 0 kV
Voltage protection level (DC+/DC- - PE) 0 kV
Specific energy (W/R) 625 kJ/Ohm
Energy-coordinated protection effect with regard to the terminal equipment No
System configuration DC No
System configuration IT Yes
System configuration TN Yes
System configuration TN-C No
System configuration TN-S Yes
System configuration TT Yes
System configuration other Yes
System configuration TN-C-S No
Voltage protection level L-PE 1.5 kV
Max. overcurrent protection device, parallel connection (fuse) 0 A
Max. overcurrent protection device, series connection (fuse) 0 A
Voltage switching spark gap technology Yes
Overcurrent protected voltage tapping No
Packing details
Packing level 1 4015081787869
Packing level 2 9008790796920
Description
For protecting consumer systems against transient overvoltages caused by direct and indirect lightning strikes and switching operations, use in accordance with IEC 60364-5-53 section 534, iI according to IEC 61643-1, SPD-type T1, T2 according to EN 61643-11, lightning protection classes III and IV as per IEC 62305